Product characteristics
| Number of inputs and outputs | Number of digital outputs: 1; Number of analog outputs: 1 |
|---|
| Probe length L [mm] | 100...1600 |
|---|
| Process connection | threaded connection G 3/4 external thread |
|---|
Application
| System | gold-plated contacts |
|---|
| Application | for industrial applications |
|---|
| Media | Liquids |
|---|
| Dielectric constant of the medium | ≥ 1,8; (for media with a dielectric constant of 1.8...5 (e.g. oils), a coaxial pipe is needed for operation) |
|---|
| Recommended media | water; water-based media; oils; oil-based media |
|---|
| Cannot be used for | See the operating instructions, chapter "Function and features". |
|---|
| Process temperature [°C] | -25...80; (90 < 1 h ; see note under remarks) |
|---|
| Pressure rating [bar] | 16 |
|---|
| Vacuum resistance [mbar] | -1000 |
|---|
| MAWP (for applications according to CRN) [bar] | 16 |
|---|
Electrical data
| Operating voltage [V] | 18...30 DC |
|---|
| Current consumption [mA] | < 30 |
|---|
| Protection class | III |
|---|
| Reverse polarity protection | yes |
|---|
| Power-on delay time [s] | < 3 |
|---|
| Measuring principle | guided wave radar |
|---|
Inputs / outputs
| Number of inputs and outputs | Number of digital outputs: 1; Number of analog outputs: 1 |
|---|
Outputs
| Total number of outputs | 2 |
|---|
| Output signal | switching signal; analog signal; IO-Link |
|---|
| Electrical design | PNP |
|---|
| Number of digital outputs | 1 |
|---|
| Output function | normally open / closed; (configurable) |
|---|
| Max. voltage drop switching output DC [V] | 2.5 |
|---|
| Permanent current rating of switching output DC [mA] | 200 |
|---|
| Number of analog outputs | 1 |
|---|
| Analog current output [mA] | 4...20, invertible; (scalable) |
|---|
| Max. load [Ω] | 500 |
|---|
| Analog voltage output [V] | 0...10, invertible; (scalable) |
|---|
| Min. load resistance [Ω] | 2000 |
|---|
| Short-circuit protection | yes |
|---|
| Type of short-circuit protection | thermal, pulsed |
|---|
| Overload protection | yes |
|---|
Measuring/setting range
| Probe length L [mm] | 100...1600 |
|---|
| Active range A [mm] | L-40; (when set to oil and oil based media: L-60) |
|---|
| Inactive range I1 / I2 [mm] | 30 / 10; (when set to oil and oil based media: 30 / 30) |
|---|
| Sampling rate [Hz] | 4 |
|---|
Setting range
| Set point SP [mm] | 15...L-30 |
|---|
| Note on setpoint SP | | when set to oil and oil based media: 35...L-30 |
|
|---|
| Reset point rP [mm] | 10... L-35 |
|---|
| Note on reset point rP | | when set to oil and oil based media: 30...L-35 |
|
|---|
| In steps of [mm] | 5 |
|---|
| Hysteresis [mm] | > 5 |
|---|
Accuracy / deviations
| Repeatability [mm] | ± 5 |
|---|
| Measuring error [mm] | ± 7 |
|---|
| Offset error [mm] | 5 |
|---|
| Resolution [mm] | 1 |
|---|
| Zero signal (voltage) [V] | 0 |
|---|
| Zero signal (current) [mA] | 4.0 |
|---|
| Full signal (voltage) [V] | 10 |
|---|
| Full signal (current) [mA] | 20 |
|---|
| Temperature drift per 10 K | ± 0.2 |
|---|
Interfaces
| Communication interface | IO-Link |
|---|
| Transmission type | COM2 (38,4 kBaud) |
|---|
| IO-Link revision | 1.1 |
|---|
| SDCI standard | IEC 61131-9 CDV |
|---|
| Profiles | no profile |
|---|
| SIO mode | yes |
|---|
| Required master port class | A |
|---|
| Process data analog | 1 |
|---|
| Process data binary | 1 |
|---|
| Min. process cycle time [ms] | 2.3 |
|---|
| Supported DeviceIDs | | Type of operation | DeviceID |
|---|
| default | 344 |
|
|---|
Operating conditions
| Ambient temperature [°C] | -25...60 |
|---|
| Storage temperature [°C] | -40...80 |
|---|
| Protection | IP 67 |
|---|
Tests / approvals
| EMC | | DIN EN 61000-6-2 | | | DIN EN 61000-6-3 | in a closed metal tank | | DIN EN 61000-6-4 | in plastic or open metal tanks |
|
|---|
| Shock resistance | | DIN EN 60068-2-27 | 50 g (11 ms) / 25 g (6 ms) with reference rod 0.5 m |
|
|---|
| Vibration resistance | | DIN EN 60068-2-6 | 5 g (10...2000 Hz) / 1 g (5...200 Hz) with reference rod 0.5 m |
|
|---|
| MTTF [years] | 196 |
|---|
| UL approval | | UL approval number | H006 | | File number UL | E174191 |
|
|---|
Mechanical data
| Weight [g] | 378.4 |
|---|
| Dimensions [mm] | Ø 50 / L = 99 |
|---|
| Material | stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); FKM; PBT; PC; PEI; TPE-V |
|---|
| Materials (wetted parts) | stainless steel (1.4305 / 303); probe connection: stainless steel (1.4435 / 316L); PTFE; FKM; sealing: NBR fiber-reinforced |
|---|
| Process connection | threaded connection G 3/4 external thread |
|---|
Displays / operating elements
| Display |
Tags:
HDL-NS24070107
|
|---|