| Product type | Single relay |
| Operating mode | 100% operating factor |
| Mechanical service life | 3x 107 cycles |
| Insulation characteristics | |
| Insulation | Basic insulation |
| Insulation characteristics | |
| Insulation | Basic insulation |
| Overvoltage category | III |
| Pollution degree | 3 |
| Service life electrical | see diagram |
| Maximum power dissipation for nominal condition | 0.41 W |
| Test voltage (Winding/contact) | 5 kV AC (50 Hz, 1 min.) |
| Test voltage (Contact/contact) | 2.5 kV AC (50 Hz, 1 min., contact/contact) |
| Coil side | |
| Nominal input voltage UN | 24 V DC |
| Input voltage range | 15.6 V DC ... 59.52 V DC |
| Drive and function | monostable |
| Drive (polarity) | non-polarized |
| Typical input current at UN | 17 mA |
| Typical response time | 7 ms |
| Typical release time | 3 ms |
| Coil resistance | 1440 Ω ±10 % (at 20 °C) |
| Switching | |
| Contact switching type | 2 changeover contacts |
| Type of switch contact | Single contact |
| Contact material | AgNi |
| Maximum switching voltage | 250 V AC/DC |
| Minimum switching voltage | 5 V (10 mA) |
| Limiting continuous current | 8 A |
| Maximum inrush current | 25 A (20 ms) |
| Min. switching current | 10 mA (5 V) |
Tags: