Product data sheet
| Range of Product | Harmony Relay |
|---|---|
| Relay Type | Voltage measurement relay |
| Product or Component Type | Industrial measurement and control relays |
| Relay name | RM4U |
| Relay monitored parameters | Overvoltage or undervoltage detection |
| time delay | Adjustable 0.05...30 s |
| Contacts type and composition | 2 C/O |
| Maximum switching voltage | 440 V AC |
|---|---|
| operating voltage tolerance | 0.85...1.1 Uc |
| Power consumption in VA | 1.9…3.3 VA AC |
| Output contacts | 2 C/O |
| Hysteresis | 5…30 % adjustable voltage threshold setting |
| Internal input resistance | 1111000 Ohm 668000 Ohm 11110000 Ohm |
| Permissible continuous overload | 550 V 400 V |
| Permissible non repetitive overload | 500 A <= 1 s 550 A <= 1 s |
| Switching threshold drift | <= 0.06 % per degree centigrade depending permissible ambient air temperature <= 0.5 % within the supply voltage range (0.85...1.1 Un) |
| Setting accuracy of time delay | 10 P |
| Time delay drift | <= 0.07 % per degree centigrade depending on the rated operational temperature <= 0.5 % within the supply voltage range (0.85...1.1 Un) |
| Quality labels | CE |
| Setting accuracy of the switching threshold | +/-5 % |
| Operating position | Any position without derating |
| Overvoltage category | III IEC 60664-1 |
| [Ui] rated insulation voltage | 500 V IEC |
| Supply disconnection value | > 0.1 Uc |
| Connections - terminals | Screw terminals, 2 x 1.5 mm²flexible with cable end Screw terminals, 2 x 2.5 mm²flexible without cable end |
| [Ie] rated operational current | 2 A 158 °F (70 °C) 24 V DC-13 IEC 60947-5-1/1991 2 A 158 °F (70 °C) 24 V DC-13 VDE 0660 3 A 158 °F (70 °C) 115 V AC-15 IEC 60947-5-1/1991 3 A 158 °F (70 °C) 115 V AC-15 VDE 0660 3 A 158 °F (70 °C) 24 V AC-15 IEC 60947-5-1/1991 3 A 158 °F (70 °C) 24 V AC-15 VDE 0660 3 A 158 °F (70 °C) 250 V AC-15 IEC 60947-5-1/1991 3 A 158 °F (70 °C) 250 V AC-15 VDE 0660 0.1 A 158 °F (70 °C) 250 V DC-13 IEC 60947-5-1/1991 0.1 A 158 °F (70 °C) 250 V DC-13 VDE 0660 0.3 A 158 °F (70 °C) 115 V DC-13 IEC 60947-5-1/1991 0.3 A 158 °F (70 °C) 115 V DC-13 VDE 0660 |
| Tightening torque | 5.31…9.74 lbf.in (0.6…1.1 N.m) |
| Mechanical durability | 30000000 cycles |
| [Ith] conventional free air thermal current | 8 A |
| Switching capacity in mA | 10 mA 12 V |
| Contacts material | 90/10 silver nickel contacts |
| Number of cables | 2 |
| Width | 0.89 in (22.5 mm) |
| Height | 3.07 in (78 mm) |
| Depth | 3.15 in (80 mm) |
| Terminals description ISO n°1 | (C-B2-B3)CO (15-16-18)OC (A1-A2)CO (25-26-28)OC |
| Output relay state | Tripped if A measured > A set |
| 9 mm pitches | 2.5 |
| Net Weight | 0.37 lb(US) (0.168 kg) |
| Electromagnetic compatibility | Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 |
|---|---|
| Ambient air temperature for operation | -4…149 °F (-20…65 °C) |
| Vibration resistance | 0.35 ms 10…55 Hz)IEC 60068-2-6 |
| Shock resistance | 15 gn 11 ms IEC 60068-2-27 |
| Standards | EN/IEC 60255-6 |
| Product Certifications | UL CSA GL |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
| Relative humidity | 15…85 % 3K3 IEC 60721-3-3 |
| IP degree of protection | IP20 IEC 60529 terminals) IP50 IEC 60529 casing) |
| Pollution degree | 3 IEC 60664-1 |
| Directives | 73/23/EEC - low voltage directive 89/336/EEC - electromagnetic compatibility |
| Resistance to electrostatic discharge | 6 kV contact IEC 61000-4-2 level 3 8 kV air IEC 61000-4-2 level 3 |
| Resistance to electromagnetic fields | 9.14 V/m (10 V/m) IEC 61000-4-3 level 3 |
| Resistance to fast transients | 2 kV IEC 61000-4-4 level 3 |
| Protection against electric shocks | 2 kV level 3 IEC 61000-4-5 |
| Disturbance radiated/conducted | CISPR 11 group 1 - class A CISPR 22 - class A |
| Dielectric test voltage | 2.5 kV |
| Non-dissipating shock wave | 4.8 kV |
Tags: