Product characteristics
| Number of inputs and outputs | Number of digital outputs: 2 |
|---|
| Measuring range | | -1...10 bar | -15...145 psi | -30...296 inHg | -100...1000 kPa |
|
|---|
| Process connection | threaded connection G 1/8 Internal thread |
|---|
Application
| System | gold-plated contacts |
|---|
| Application | for industrial applications |
|---|
| Media | compressed air |
|---|
| Conditionally suitable for | other media on request |
|---|
| Medium temperature [°C] | 0...60 |
|---|
| Min. bursting pressure | | 30 bar | 435 psi | 886 inHg | 3000 kPa |
|
|---|
| Pressure rating | | 20 bar | 290 psi | 591 inHg | 2000 kPa |
|
|---|
| Vacuum resistance [mbar] | -1000 |
|---|
| Type of pressure | relative pressure; vacuum |
|---|
Electrical data
| Operating voltage [V] | 18...32 DC; (to SELV/PELV) |
|---|
| Current consumption [mA] | < 50 |
|---|
| Min. insulation resistance [MΩ] | 100; (500 V DC) |
|---|
| Protection class | III |
|---|
| Reverse polarity protection | yes |
|---|
| Overvoltage protection | yes; (< 40 V) |
|---|
| Power-on delay time [s] | 0.3 |
|---|
| Integrated watchdog | yes |
|---|
Inputs / outputs
| Number of inputs and outputs | Number of digital outputs: 2 |
|---|
Outputs
| Total number of outputs | 2 |
|---|
| Output signal | switching signal |
|---|
| Electrical design | PNP |
|---|
| Number of digital outputs | 2 |
|---|
| Output function | normally open / closed; (configurable) |
|---|
| Max. voltage drop switching output DC [V] | 2 |
|---|
| Permanent current rating of switching output DC [mA] | 100 |
|---|
| Switching frequency DC [Hz] | < 200 |
|---|
| Short-circuit protection | yes |
|---|
| Type of short-circuit protection | yes (non-latching) |
|---|
Measuring/setting range
| Measuring range | | -1...10 bar | -15...145 psi | -30...296 inHg | -100...1000 kPa |
|
|---|
| Set point SP | | -0.9...10 bar | -13...145 psi | -26...296 inHg | -90...1000 kPa |
|
|---|
| Reset point rP | | -0.95...9.95 bar | -14...144 psi | -28...294 inHg | -95...995 kPa |
|
|---|
| In steps of | |
|---|
Accuracy / deviations
| Switch point accuracy [% of the span] | < ± 0,5 |
|---|
| Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) |
|---|
| Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
|---|
| Hysteresis deviation [% of the span] | < ± 0,25 |
|---|
| Long-term stability [% of the span] | < ± 0,05; (per 6 months) |
|---|
| Temperature coefficient zero point [% of the span / 10 K] | 0,2; (0...60 °C) |
|---|
| Temperature coefficient span [% of the span / 10 K] | 0,2; (0...60 °C) |
|---|
Reaction times
| Response time [ms] | < 2.5 |
|---|
| Delay time programmable dS, dr [s] | 0; 0,002...5 |
|---|
Software / programming
| Parameter setting options | hysteresis / window; normally open / closed; Diagnostic function; switching logic; switch-on/switch-off delay; Damping; Display unit |
|---|
Operating conditions
| Ambient temperature [°C] | 0...70 |
|---|
| Storage temperature [°C] | -25...85 |
|---|
| Protection | IP 65 |
|---|
Tests / approvals
| EMC | | EN 61000-4-2 ESD | 4 kV CD / 8 kV AD | | EN 61000-4-3 HF radiated | 10 V/m | | EN 61000-4-4 Burst | 2 kV | | EN 61000-4-5 Surge | 0,5/1 kV | | EN 61000-4-6 HF conducted | 10 V |
|
|---|
| Shock resistance | | DIN IEC 68-2-27 | 50 g (11 ms) |
|
|---|
| Vibration resistance | | DIN IEC 68-2-6 | 20 g (10...2000 Hz) |
|
|---|
| MTTF [years] | 455 |
|---|
| Pressure equipment directive | sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
|---|
Mechanical data
| Weight [g] | 84.5 |
|---|
| Material | PBT; FKM; polyester |
|---|
| Materials (wetted parts) | brass; FKM; silicon (coated); PBT |
|---|
| Min. pressure cycles | 50 million |
|---|
| Process connection | threaded connection G 1/8 Internal thread |
|---|
Displays / operating elements
| Display | | Display unit | 4 x LED, green | | Switching status | 2 x LED, yellow | | Function display | alphanumeric display, 4-digit | | Measured values | alphanumeric display, 4-digit |
|
|---|
| Display unit | bar; kPa; psi; inHg |
|---|
Accessories
| Accessories (optional) | | mounting set for DIN rail: TH 35-7,5 / EN60715, E37340 | | Thread extension: 1/8", E30075 | | push-in air fitting for tube: Ø 6 mm, E30076 | | push-in air fitting for tube: Ø 8 mm, E30077 |
|
|---|
Electrical connection
Tags:
HDL-DYT24070105