Product data sheet
| Range of Product | Phaseo Dedicated |
|---|---|
| Product or Component Type | Power supply |
| Power supply type | Regulated switch mode |
| Kw Rating | 150 W |
| Main Input Voltage | 100...120 V AC single phase 200...240 V AC single phase 180...370 V DC |
| Output voltage | 24 V DC |
| Power supply output current | 6.2 A |
| Operating position | Any position |
| Vibration resistance | 2 gn 9…150 Hz)EN/IEC 61131-2 3.5 mm 5…9 Hz)EN/IEC 61131-2 |
| Name of test | Conducted interference EN 61000-4-8 level 4 Electrostatic discharges EN/IEC 61000-4-2 level 3 Induced electromagnetic field EN/IEC 61000-4-6 level 3 Radiated electromagnetic field EN/IEC 61000-4-3 level 3 Rapid transient IEC 61000-4-4 level 3 Conducted/radiated emissions EN 55022 Class B Conducted/radiated emissions EN/IEC 55011 Emission EN/IEC 61000-6-3 Primary outage IEC 61000-4-11 Surge EN/IEC 61000-4-5 |
| Input voltage limits | 170...264 V 85...132 V |
|---|---|
| Network Frequency | 47...63 Hz |
| Inrush current | 50 A 115 V AC 100 A 230 V AC |
| Cos phi | 0.65 |
| Efficiency | 80 % |
| Power dissipation in W | 37.5 W |
| Current consumption | 5 A 100 V 2.5 A 240 V |
| Input protection type | Integrated fuse (not interchangeable) |
| Output voltage limits | 21.6...26.4 V |
| Line and load regulation | +/- 3 % |
| Holding time | >= 10 ms 100 V >= 40 ms 240 V |
| Output protection type | Against overload 1.1...1.5 x In Against overvoltage tripping if U > 1.25 x Un Against short-circuits automatic reset Thermal |
| Connections - terminals | Ground connection screw type terminals 1 x 4 mm² AWG 12 Input connection screw type terminals 2 x 4 mm² AWG 12 Output connection screw type terminals 4 x 4 mm² AWG 12 |
| Marking | CE |
| Mounting Support | Reversible mounting bracket Panel |
| Operating altitude | 6561.68 ft (2000 m) |
| Output coupling | Series Parallel |
| Overvoltage category | II |
| Meantime between failure [MTBF] | 100000 h 104 °F (40 °C) |
| Status LED | 1 LED (Green) output voltage |
| Net Weight | 1.61 lb(US) (0.73 kg) |
| Product Certifications | TUV 60950-1 KC RCM cCSAus CSA 22-2 No 60950-1 EAC UL 508 |
|---|---|
| Environmental characteristic | EMC EN 50081-1 EMC EN 50082-2 EMC EN 61000-6-3 EMC EN/IEC 61000-6-2 Safety EN/IEC 60950-1 Safety SELV |
| IP degree of protection | IP20 conforming to EN/IEC 60950 |
| Ambient air temperature for operation | 32…113 °F (0…45 °C) without derating) 113…140 °F (45…60 °C) with derating factor) |
| Ambient Air Temperature for Storage | -13…185 °F (-25…85 °C) |
| Relative humidity | 20…90 % |
| Overvoltage category | Class I VDE 0106-1 |
| Pollution degree | 2 |
| Dielectric strength | 1500 V between input and ground 3000 V between input and output 500 V between output and ground |
Tags: