Product data sheet
Technical data
| Number of analog inputs | 2 | 
| Total number of channels (module) | 2 | 
| Signal type | Current | 
| Signal type (current) | 4 … 20 mADC | 
| Sensor connection | 2 x (2-wire) | 
| Input voltage (max.) | 35 V | 
| Signal characteristics | Differential | 
| Resolution [bit] | 12Bit | 
| Input resistance (max.) | 220Ω | 
| Data width | 2 x 16-bit data; 2 x 8-bit control/status (optional) | 
| Conversion time (typ.) | 2ms | 
| Measurement error (reference temperature) | 25°C | 
| Measurement error, deviation (max.) from the upper-range value | 0.2% | 
| Temperature error (max.) of the upper-range value | 0.01%/K | 
| Supply voltage (system) | 5 VDC; via data contacts | 
| Current consumption (5 V system supply) | 70mA | 
| Isolation | 500 V system/field | 
| Indicators | LED (A, C) green: Function AI 1, AI 2; LED (B, D) red: Error AI 1, AI 2 | 