Product data sheet
| Mechanical durability | 3000000 cycles | 
|---|---|
| Contact code designation | A600 AC-15, Ue = 240 V, Ie = 3 A conforming to IEC 947-5-1 appendix A A600 AC-15, Ue = 600 V, Ie = 1.2 A conforming to IEC 947-5-1 appendix A Q600 DC-13, Ue = 250 V, Ie = 0.27 A conforming to IEC 947-5-1 appendix A Q600 DC-13, Ue = 600 V, Ie = 0.1 A conforming to IEC 947-5-1 appendix A  | 
| [Ithe] conventional enclosed thermal current | 10 A | 
| [Ui] rated insulation voltage | 600 V (pollution degree 3) conforming to IEC 60947-1 | 
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-1 | 
| Maximum resistance across terminals | 25 MOhm | 
| Operating force | 3…5 N | 
| Short-circuit protection | 10 A fuse protection by cartridge fuse type gG (gl) | 
| Rated operational power in W | 40 W DC-13 for 1000000 cycles, operating rate <3600 cyc/h at 120 V, load factor = 0.5 conforming to IEC 60947-5-1 48 W DC-13 for 1000000 cycles, operating rate <3600 cyc/h at 48 V, load factor = 0.5 conforming to IEC 60947-5-1 65 W DC-13 for 1000000 cycles, operating rate <3600 cyc/h at 24 V, load factor = 0.5 conforming to IEC 60947-5-1  | 
| Terminals description ISO n°1 | (13-14)NO | 
| net weight | 0.015 kg | 
| Height | 29 mm | 
| Width | 15 mm | 
| Depth | 24 mm | 
| Connections - terminals | Screw clamps terminals | 
| Fixing collar material | Zamak | 
| Connections - terminals | Screw clamps terminals, 1 x 2.5 mm² with or without cable end Screw clamps terminals, 2 x 1.5 mm² with or without cable end  | 
| Contacts material | Silver alloy (Ag/Ni) | 
| Contacts usage | Standard contacts | 
| Connections - terminals | Screw clamp terminal, <= 2 x 1.5 mm² with and without cable ends Screw clamp terminal, <= 1 x 2.5 mm² with and without cable ends Screw clamp terminal, >= 1 x 0.5 mm² with and without cable ends Faston terminals, connection size: 6.3 mm  | 
| Electrical durability | 1000000 cycles, AC-15, 3 A at 240 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 1000000 cycles, DC-13, 0.27 A at 250 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C  | 
| Electrical reliability | Λ < 10exp(-6) at 5 V, 1 mA in clean environment conforming to IEC 60947-5-4 Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to IEC 60947-5-4  | 
| [Ie] rated operational current | 3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1 0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1  | 
| Short-circuit protection | 10 A gL fuse type gG conforming to IEC 60947-5-1 | 
| [Ith] conventional free air thermal current | 10 A conforming to IEC 60947-5-1 | 
| Positive opening | Without | 
| Operating travel | 2.38 mm (NO changing electrical state) 5 mm (total travel)  | 
| Shape of screw head | Cross compatible with Philips no 1 screwdriver Cross compatible with pozidriv No 1 screwdriver Slotted compatible with flat Ø 4 mm screwdriver Slotted compatible with flat Ø 5.5 mm screwdriver  | 
| protective treatment | TC/TH | 
| customizable | No | 
| Shock resistance | 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27  | 
| Tightening torque | 0.8…1.0 N.m | 
| Fixing mode | Fixing screw beneath head recommended torque: 0.8 N.m Fixing screw beneath head recommended torque: 1.0 N.m  | 
          Tags:
                      HDL-QL24070804
                              
                  
     
      
      
          
                    